COOLUNIT MKZ 1,200 - Mobile Chiller Units

The chiller can be positioned outdoors on any suitable soil. It must howevewr be level horizontally.

  • Mobile Chiller Unit 1,200 kW
  • Your advantages 

    • Fitted with three extremely quiet screw compressors
    • The shell and tube evaporator is designed as highly efficient heat exchanger
    • The entire control system is integrated into the housing

The following free space requirements are to be observed. At least 1.80 m on three sides and 3.50 m on one side.

Power connection:
An electric power supply is required (400 V / 50 Hz / 3 Ph + N + PE +/- 5 %).  2 x 500 A fuses, cable cross section 2 x 240 mm² single core cables. A professional electrician is to be charged with connecting the power connection to the building.

Technical data MKZ 1,200

 
Cooling output 7/12°C und 35°C ambient temperature
kW
1,238
Refrigerant
Frigen
R134A
Compressor
McQuay        
Screw
Water connections
Inch
Bauer 4"
Electrical power supply
kW
480
Current consumption
A
869
Power supply
V / Hz / Ph  
400/50/3 +/-5%
Elektrical connection
mm²
2 x 240
Sound pressure level at 10 m
db(A)
68
Water volume
m³/h
232
Max. permissible system pressure
bar
6
Dimensions L x W x H
mm
11,000 x 2,230 x 2,520       
Transport-/operating weight
kg
9,750 / 10,160
 
Subject to technical changes