COOLUNIT MKZ 1,200 - Mobile Chiller Units
The chiller can be positioned outdoors on any suitable soil. It must howevewr be level horizontally.
-
Your advantages
- Fitted with three extremely quiet screw compressors
- The shell and tube evaporator is designed as highly efficient heat exchanger
- The entire control system is integrated into the housing
The following free space requirements are to be observed. At least 1.80 m on three sides and 3.50 m on one side.
Power connection:
An electric power supply is required (400 V / 50 Hz / 3 Ph + N + PE +/- 5 %). 2 x 500 A fuses, cable cross section 2 x 240 mm² single core cables. A professional electrician is to be charged with connecting the power connection to the building.
Additional equipment
Technical data MKZ 1,200
Cooling output 7/12°C und 35°C ambient temperature | kW | 1,238 |
Refrigerant | Frigen | R134A |
Compressor | McQuay | Screw |
Water connections | Inch | Bauer 4" |
Electrical power supply | kW | 480 |
Current consumption | A | 869 |
Power supply | V / Hz / Ph | 400/50/3 +/-5% |
Elektrical connection | mm² | 2 x 240 |
Sound pressure level at 10 m | db(A) | 68 |
Water volume | m³/h | 232 |
Max. permissible system pressure | bar | 6 |
Dimensions L x W x H | mm | 11,000 x 2,230 x 2,520 |
Transport-/operating weight | kg | 9,750 / 10,160 |
Subject to technical changes | ||